HV disconnector with earthing switch

Outdoor three-pole disconnector on four tubular columns and cross beams. Centre-break: two rotating post insulators per phase on bearings, carrying contact arms that meet in the middle (male and finger contacts) and swing 90° to the same side as open goes to 1. Pantograph: a support insulator and a rotating operating insulator, with scissor arms folding as it opens. Each phase has a hinged earthing blade that rises to the terminal when earthed and the main contacts are open. Motor operating mechanism with drive shaft and interphase coupling rods; manual earthing-switch mechanism.

IEC 62271-102IEC 62271-1IEC 60273IEC 61936-1
Drag to orbit, scroll to zoom
Parameters
–

Installation

$npx -y https://decktwin.com/cli/deck-twin-0.2.2.tgz add disconnector

Copies onshore/disconnector.tsx and the shared lib/ into src/components/deck-twin/. Needs three, @react-three/fiber and @react-three/drei. See installation for the manual route.

Usage

import { Canvas } from '@react-three/fiber'
import { OrbitControls } from '@react-three/drei'
import { Stage } from './components/deck-twin/lib/stage'
import { Disconnector } from './components/deck-twin/onshore/disconnector'

export default function Scene() {
  return (
    <Canvas shadows camera={{ position: [8, 5, 9], fov: 35 }}>
      <Stage>
        <Disconnector />
      </Stage>
      <OrbitControls makeDefault />
    </Canvas>
  )
}

Props

PropTypeDefaultRange
kv72.5 | 145 | 245 | 420null
style"centre-break" | "pantograph"null
opennumbernull0 – 1
earthedbooleannull
insulation"porcelain" | "composite"null
tagstringnull
...groupposition, rotation, scale…

P&ID

P&ID symbol for disconnector

Single-line: a switch blade with a short bar across the fixed contact (disconnector), usually next to an earthing switch drawn as a second blade going to the earth symbol (three shortening lines).

tag QBtag QCIEC 60617 (single-line diagram); IEC 62271-102

Bar on the contact = disconnector (isolator, no load breaking); × = circuit breaker. Some drawings tag disconnectors DS. ANSI device numbers are 89 for the disconnector and 57 for the earthing switch.

HV disconnector datasheet (IEC 62271-102) fields and the props they set
Rated voltagekv
Stylestyle
External insulationinsulation
Tag numbertag

Typical suppliers

Hitachi Energy. The geometry is generic and sized from public standards. It is not vendor CAD.

For agents

Machine-readable entry with props, ranges, defaults and ports:

$npx -y https://decktwin.com/cli/deck-twin-0.2.2.tgz info disconnector

Or fetch /r/disconnector.json, or copy a ready-made instruction:

Add the Deck Twin "HV disconnector with earthing switch" component to this project. Run `npx -y https://decktwin.com/cli/deck-twin-0.2.2.tgz add disconnector` (it copies the file and the shared lib into src/components/deck-twin/), then `npx -y https://decktwin.com/cli/deck-twin-0.2.2.tgz info disconnector` for its props, ranges and ports. Render <Disconnector /> inside a React Three Fiber <Canvas shadows>, wrapped in <Stage> from src/components/deck-twin/lib/stage. Set props from my data (metres, NPS in inches, ASME class) and leave the rest at defaults. Install three, @react-three/fiber, @react-three/drei and @types/three if they're missing. Full guide: https://decktwin.com/skill/SKILL.md