IEC 61508 vs IEC 61511
Functional safety for any industry, and functional safety for the process industry
The short answer
IEC 61508 is the basic, cross-industry standard for the functional safety of electrical, electronic and programmable electronic safety-related systems, and it is used mainly by the makers of safety devices. IEC 61511 is the process industry standard. It applies the principles of 61508 for the people who specify, design, integrate, operate and maintain safety instrumented systems. On an oil and gas plant the SIS is engineered to IEC 61511, and its transmitters, logic solvers and valves are either assessed to IEC 61508 or justified by prior use.
Side by side
| IEC 61508 | IEC 61511 | |
|---|---|---|
| What it is | Functional safety of electrical, electronic and programmable electronic safety-related systems | Functional safety: safety instrumented systems for the process industry sector |
| Issued by | IEC | IEC |
| Structure | Seven parts | Three parts |
| Sector | Any industry. It is the basis for sector standards | The process industry, including oil and gas |
| Main users | Makers and suppliers of safety devices and systems | End users, designers and integrators of safety instrumented systems |
| Life cycle | The full safety life cycle, including hardware and software development | The SIS life cycle, from hazard and risk assessment to decommissioning |
| Safety integrity levels | Defines SIL 1 to SIL 4 | Uses the same SILs. Process functions are usually SIL 1 to SIL 3 |
| Device selection | Sets the requirements a device is assessed against | Accepts devices assessed to IEC 61508, or selected on the basis of prior use |
| National adoption | Published in Europe as EN 61508 | Adopted in the US as ANSI/ISA-61511-2018. The earlier US adoption was ANSI/ISA-84.00.01-2004 |
A summary in our own words. Check the editions your project names, and the national adoption that applies.
Who uses which
The split is between making devices and building systems from them. A maker designing a safety transmitter, a logic solver or a valve actuator follows IEC 61508, and an assessment against it gives the device its SIL capability.
The operator and its engineering contractor follow IEC 61511. They work out which safety instrumented functions are needed and to which SIL, design the SIS, prove it meets the target, and then operate, test and maintain it.
How they are used together
IEC 61511 applies the principles of IEC 61508 to the process industry, in its own terms. It points back to 61508 for devices that are not justified by prior use.
On a typical project, the hazard study and SIL assessment are done to 61511. The SIS vendor supplies a logic solver certified to 61508, and the instrument and valve vendors supply 61508 data or prior-use evidence for their devices. The final calculations and proof test intervals are done under 61511.
Common confusions
A SIL-certified device does not make a SIL-rated function. The SIL belongs to the whole function, from sensor to final element, and is proven under 61511.
IEC 61511 is written for a different audience rather than as a lighter copy of 61508. It covers the same principles and adds the process-plant steps such as hazard and risk assessment and operation.
ISA 84 and IEC 61511 work together. The current US standard, ANSI/ISA-61511, is the IEC standard adopted without modification.
How it shows up on a project
The safety requirements specification lists each safety instrumented function with its SIL target, written to IEC 61511. Device datasheets and vendor safety manuals give the 61508 data, such as the SIL capability and failure rates, or the prior-use justification. The cause and effect chart shows what each function does.
Questions
Is IEC 61511 the same as IEC 61508?
No. IEC 61508 is the basic standard for any industry and is used mainly by device makers. IEC 61511 is the process industry standard for designing and running safety instrumented systems. It applies the principles of 61508 and points back to it for devices not justified by prior use.
Which standard applies to a safety instrumented system on an oil and gas plant?
IEC 61511, or its national adoption such as ANSI/ISA-61511 in the US. The devices inside the system are assessed to IEC 61508 or justified by prior use.
Does every SIS device need IEC 61508 certification?
Not always. IEC 61511 also lets a user select a device on the basis of documented prior use in similar service. Many projects still ask for 61508 certified devices where they are available.
What is ISA 84?
The ISA committee and standard for safety instrumented systems in the US. ANSI/ISA-84.00.01-2004 adopted IEC 61511 with a clause for existing systems, and the current US standard is ANSI/ISA-61511-2018.
This page explains two standards in plain words. It is not a substitute for the standards themselves, and project specifications often add to both. Deck Twin uses these standards as reference values for visualisation. Check the current edition of each standard before using any value for design, procurement or fabrication.