IEC 61511

Functional safety: safety instrumented systems for the process industry

IEC 61511 explained: the process industry SIS standard, its three parts, the safety lifecycle, SIL 1 to 4 and how it relates to IEC 61508.

Scope

IEC 61511 sets out how to specify, design, install, operate, maintain and modify safety instrumented systems (SIS) in the process industry. An SIS is a set of sensors, a logic solver and final elements, such as shutdown valves, that takes the process to a safe state when a hazardous condition is detected. Each protective function it performs is a safety instrumented function (SIF) with a target safety integrity level (SIL).

On oil and gas facilities the SIS carries the high-integrity trips: high-high level and pressure shutdowns, compressor trips, burner management and emergency shutdown. The standard is used by operators, engineering contractors and system integrators, and its US adoption is ANSI/ISA-61511.

It is the process sector version of IEC 61508. Device makers prove their products to IEC 61508, and the process plant uses those products under IEC 61511. It does not cover the design of the basic process control system in general. It does limit what can be claimed for it: a BPCS protection layer counted for more than a risk reduction of 10 must itself be designed and managed to IEC 61511.

The three parts of IEC 61511

PartTitleWhat it is for
IEC 61511-1Framework, definitions, system, hardware and application programming requirementsThe requirements: the lifecycle, management of functional safety, design and verification
IEC 61511-2Guidelines for the application of IEC 61511-1Guidance on how to meet Part 1, clause by clause
IEC 61511-3Guidance for the determination of the required safety integrity levelsMethods for SIL determination, such as risk graphs and layer of protection analysis

The current parts are edition 2.0 of 2016. Part 1 has an amendment from 2017, and a consolidated edition 2.1 combines them. ANSI/ISA-61511-1, -2 and -3 of 2018 adopt them in the US. Check the IEC webstore for the current status.

The safety lifecycle

  1. 1

    Hazard and risk assessment

    The hazards of the process are found, often in a HAZOP, and the risk of each is compared with the target the company accepts.

  2. 2

    Allocation and SIL determination

    Each risk reduction is allocated to a protection layer. Where an instrumented function is needed, its SIL is set, often by layer of protection analysis (LOPA).

  3. 3

    Safety requirements specification

    The SRS states what each SIF must do: what it senses, its trip point, what it closes or stops, how fast, its SIL and how often it is tested.

  4. 4

    Design and verification

    The SIS is designed to the SRS. Calculations show that each SIF meets its SIL target for hardware failure, with enough fault tolerance and proven or certified devices.

  5. 5

    Installation, commissioning and validation

    The installed system is checked against the SRS before the hazards are introduced.

  6. 6

    Operation, maintenance and proof testing

    Proof tests at the intervals in the SRS find failures that the system cannot detect by itself. Demands, faults and bypasses are recorded.

  7. 7

    Modification and decommissioning

    Any change goes through management of change and returns to the right step of the lifecycle.

SIL levels and risk reduction

In the process industry most SIFs are in low demand mode: they are called on no more than once a year. Their SIL is set by the average probability of failure on demand (PFDavg). The table shows the commonly quoted bands from IEC 61508 and IEC 61511.

SILPFDavg, low demandRisk reduction factor
SIL 10.01 to 0.110 to 100
SIL 20.001 to 0.01100 to 1,000
SIL 30.0001 to 0.0011,000 to 10,000
SIL 40.00001 to 0.000110,000 to 100,000

Commonly quoted values, not a copy of the standard. SIL 4 is rarely used in the process industry. High demand and continuous mode functions use a probability of failure per hour instead.

Key concepts

Safety instrumented function
One protective function, such as close the inlet ESD valve on high-high separator level. It has a sensor, logic and a final element, a trip point, a response time and a SIL.
Safety integrity level
A measure of how much risk reduction a SIF must give, from SIL 1 to SIL 4. It sets the target failure probability, the architecture and the rigour of the work done on the function.
Independent protection layers
An SIS is one of several layers, with the control system, alarms with operator response, relief valves and physical barriers. LOPA counts only layers that are independent of the cause and of each other.
Hardware fault tolerance
The number of faults a function can have and still work. Higher SILs need more redundancy, such as two transmitters voted one out of two or two out of three.
Proven in use and certified devices
Devices are selected either because they are certified to IEC 61508 or because there is enough operating history to show that they are reliable in similar service.
Functional safety assessment
Independent reviews at set points in the lifecycle check that the SIS meets the standard and the SRS. The competence of the people doing the work is also a requirement.

Questions

What is IEC 61511?

IEC 61511 is the international standard for safety instrumented systems in the process industry. It sets out a lifecycle, from hazard assessment through design, operation and modification, and requires each safety instrumented function to meet a safety integrity level. It has three parts.

What is the difference between IEC 61508 and IEC 61511?

IEC 61508 is the general functional safety standard, used mainly by the makers of safety devices and systems. IEC 61511 applies those ideas to process plants and is used by the operators and engineers who build the SIS from those devices. See IEC 61508 vs IEC 61511.

What does SIL 2 mean?

A SIL 2 function must reduce the risk by a factor of 100 to 1,000. In low demand mode, its average probability of failing when called on must be between 0.001 and 0.01. Meeting that number is only part of it: the architecture, the devices and the way the work is done must also meet SIL 2 requirements.

Is ISA 84 the same as IEC 61511?

The US adopted IEC 61511 as ANSI/ISA-84.00.01-2004, with a small modification for existing systems. The later US adoption is ANSI/ISA-61511 of 2018, which is the IEC text. ISA 84 is still the name of the committee and of the related technical reports.

In Deck Twin

The ESD valve and blowdown valve cite IEC 61508 and 61511 as the final elements of safety instrumented functions, and the fire alarm panel cites IEC 61511 for its SIS role. The library models the hardware. It does not set SIL targets, calculate PFDavg or show that any function meets IEC 61511.

Deck Twin uses these standards as reference values for visualisation. Check the current edition of each standard before using any value for design, procurement or fabrication.

Components that follow IEC 61511 3