NFPA 20 vs NFPA 25

Installing a fire pump, and keeping it working

The short answer

NFPA 20 covers how a stationary fire pump is selected and installed: the pump, its driver and controller, the piping around it and the acceptance test. NFPA 25 covers what happens afterwards: the inspection, testing and maintenance of fire pumps and other water-based fire protection systems for their whole life. A firewater pump is designed and commissioned to NFPA 20 and kept in service to NFPA 25.

Side by side

NFPA 20NFPA 25
What it isStandard for the Installation of Stationary Pumps for Fire ProtectionStandard for the Inspection, Testing, and Maintenance of Water-Based Fire Protection Systems
Issued byNFPANFPA
When in the lifeSelection, installation and acceptanceFrom commissioning onward, for the life of the system
Systems coveredStationary fire pumps, drivers and controllersFire pumps and other water-based systems: sprinklers, standpipes, private fire service mains, water storage tanks, water spray, foam-water and water mist
Main usersDesigners, installers and pump packagersOwners, maintenance contractors and inspectors
TestingAcceptance testing at commissioningRoutine inspections and run tests, and an annual flow test of each fire pump
ResponsibilityThe design and installation teamThe owner, using qualified people
How they relateSets the pump installation and its acceptance testChecks the pump still performs as it did at acceptance

A summary in our own words. Test intervals and acceptance criteria vary between editions, so use the edition the authority having jurisdiction enforces.

When each one applies

During design, purchase, installation and acceptance, the pump set follows NFPA 20. Once it is in service, NFPA 25 takes over for inspection, testing and maintenance.

NFPA 20 does not size the firewater demand. That comes from the fire protection design, such as NFPA 15 water spray and deluge zones.

How they are used together

The acceptance test under NFPA 20 records how the new pump performs across its curve. NFPA 25 then has the pump run on a regular schedule and flow tested every year, and the results are compared with the acceptance test and the maker's curve. A falling result is a sign that the pump, its driver or its water supply needs attention.

Offshore and outside the US

Neither standard applies offshore automatically. Offshore projects adopt NFPA 20 through the project specification, usually with changes for caisson pumps, hazardous areas and the rules of the classification society or regulator.

Testing and maintenance offshore are run through the operator's maintenance system. Many operators base the routines on NFPA 25, adjusted to the regulator's rules and the installation's own performance standards.

Common confusions

NFPA 20 and NFPA 25 are separate standards for different stages of the pump's life, not two editions of one document.

NFPA 25 covers more than pumps. Sprinklers, standpipes, water spray systems and tanks are in it too.

A good acceptance test says nothing about the pump five years on. That is what the NFPA 25 schedule is for.

Questions

What is the difference between NFPA 20 and NFPA 25?

NFPA 20 covers how a fire pump is selected and installed. NFPA 25 covers what happens afterwards: the inspection, testing and maintenance of fire pumps and other water-based fire protection systems.

Which NFPA standard covers fire pump testing?

Both, at different stages. The acceptance test at commissioning is covered by NFPA 20. Routine run tests and the annual flow test in service are covered by NFPA 25.

How often must a fire pump be flow tested?

NFPA 25 calls for an annual flow test of each fire pump, with run tests in between on a schedule that depends on the driver and the edition in force. Use the edition the authority having jurisdiction enforces.

Does NFPA 25 apply to offshore firewater pumps?

Only where the operator or regulator adopts it. Offshore, testing and maintenance run through the operator's maintenance system, which often draws on NFPA 25 together with the regulator's rules.

This page explains two standards in plain words. It is not a substitute for the standards themselves, and project specifications often add to both. Deck Twin uses these standards as reference values for visualisation. Check the current edition of each standard before using any value for design, procurement or fabrication.

Components that follow NFPA 20 or NFPA 25