ASME B31.1
Power piping
ASME B31.1 power piping code in plain words: what it covers, boiler external piping, design and testing, and how it differs from B31.3.
Scope
ASME B31.1 is the code for power piping. It covers the piping in electric power generating stations, industrial and institutional plants, geothermal heating systems and central and district heating and cooling systems. It sets rules for materials, design, fabrication, erection, examination and testing. It also covers boiler external piping: the piping from a power boiler out to the stop valves that the boiler code requires, where the boiler code and the piping code meet.
On oil and gas facilities B31.1 is less common than B31.3, because most piping on a process plant carries hydrocarbons and follows the process piping code. B31.1 is used where a facility has a power plant or a steam system of the utility type: steam and condensate lines around a packaged boiler, a waste heat recovery unit on a gas turbine exhaust, or a cogeneration plant at a refinery or gas plant. The project specification says where the boundary between the two codes lies.
It does not cover process piping (ASME B31.3), pipelines (ASME B31.4 and B31.8) or the boiler itself (ASME Section I). ASME issues a new edition every few years, and the current one is B31.1-2026.
Where B31.1 applies
The code applies to the piping system as a whole: pipe, fittings, flanges, valves, bolting, supports and hangers. Components made to a standard listed in the code, such as ASME B16.5 flanges or ASME B16.9 fittings, are accepted within their ratings.
Boiler external piping is a special case. It is designed under B31.1 but falls under the jurisdiction of the boiler code, so it needs the inspection, stamping and documentation the boiler code requires. Main steam and feedwater lines close to the boiler are typical examples.
B31.1 and B31.3 side by side
The two codes share most of their design approach and differ mainly in the plants and fluids they cover. ASME B31.3 vs B31.1 compares them in more detail.
| ASME B31.1 Power piping | ASME B31.3 Process piping | |
|---|---|---|
| Typical plants | Power stations, boiler houses, district heating, utility steam | Refineries, chemical plants, gas plants, offshore topsides |
| Typical fluids | Steam, condensate, feedwater, fuel, air, water | Hydrocarbons, chemicals, gases, and utilities inside the plant |
| Fluid categories | Not split by fluid hazard in the same way | Normal, Category D, Category M, High Pressure, elevated temperature, high purity |
| Boiler interface | Covers boiler external piping | Does not cover boiler external piping |
| Long-term high temperature | A main design concern for steam lines | Covered, but less often the governing case |
A plain comparison of the scopes, not a copy of either code.
Testing
New piping is normally given a hydrostatic leak test. The commonly quoted minimum test pressure is 1.5 times the design pressure, limited so that no component is stressed beyond what the code allows. Pneumatic testing and initial service leak testing are allowed under stated conditions.
Boiler external piping is hydrostatically tested to the boiler code rules. Check the current edition for the exact conditions and limits.
Key concepts
- Power piping
- Piping that serves power generation and the plant around it: steam, feedwater, condensate, blowdown, fuel and auxiliary systems.
- Boiler external piping
- The piping between a power boiler and the stop valves the boiler code requires on its steam, feedwater and other connections. It is built to B31.1 and is inspected and certified under the boiler code.
- High-temperature design
- Main steam lines run hot for decades, so creep and long-term strength set the allowable stress. Material choice, weld quality and heat treatment get extra attention on these lines.
- Allowable stress
- The code gives allowable stresses for listed materials at each temperature. Wall thickness is calculated from the design pressure, diameter and allowable stress, then allowances for corrosion and mill tolerance are added.
- Flexibility and supports
- Hot lines grow as they heat up. The layout and the hangers must take that movement without overloading the pipe, the equipment nozzles or the supports. Spring hangers and constant-load supports are common on steam lines.
- Examination
- Welds are examined visually and, depending on the service and conditions, by radiography or ultrasonic testing. The required extent depends on pressure, temperature and the type of weld.
Questions
What is the difference between ASME B31.1 and B31.3?
B31.1 is for power piping: steam, water and utility systems in power stations and boiler plants, including boiler external piping. B31.3 is for process piping in refineries, chemical and gas plants. On an oil and gas facility, the process piping is B31.3 and a utility steam system can be B31.1. See ASME B31.3 vs B31.1.
What is the current edition of ASME B31.1?
ASME lists B31.1-2026 as the current edition. Editions come out every few years, and a project normally names the edition it is designed to.
What is the hydrostatic test pressure in ASME B31.1?
The commonly quoted minimum is 1.5 times the design pressure. The test pressure must not stress any component past the limit the code allows, so the ratings of valves and flanges in the test section can cap it.
Does ASME B31.1 apply to offshore platforms?
Not usually to the process piping, which is B31.3. Some operators use B31.1 for utility steam or heating systems on a platform, but many offshore piping specifications put all topsides piping under B31.3.
In Deck Twin
No component cites ASME B31.1. The packaged boiler, which cites ASME Section I, and the steam trap are the components closest to its scope, and the pipe spool, elbow and weld neck flange use ASME B36.10 and B16 dimensions that B31.1 lists. The library does not design piping to B31.1 or any other code.
Deck Twin uses these standards as reference values for visualisation. Check the current edition of each standard before using any value for design, procurement or fabrication.