Valve actuator symbols on a P&ID

An actuator sits on top of the valve stem. The body below gives the valve type and the head shows how it is moved. On most legends a dome is a pneumatic diaphragm, a rectangle a piston cylinder, a circle with M an electric motor and a box with S a solenoid. The marks here follow ISA 5.1 and PIP PIC001. The fail position is written as letters under the body or drawn on the stem.

25 symbols.

How to read these symbols

Reading the head

A bar on a stem is a handwheel, a slanted line a lever and a small square with a side shaft a gear operator. A dome on a flat bar is a spring-diaphragm actuator, the usual head on a modulating control valve. A rectangle with a piston line is a cylinder. With a spring drawn in it the actuator is spring return, and with a signal port at each end it is double acting. EH marks an electro-hydraulic actuator and H a hydraulic one.

Fail position

An actuated valve goes to its fail position when it loses air, power or signal. Most legends write FO (fail open), FC (fail closed) or FL (fail locked in the last position) just below the body, and some add FI (fail indeterminate). Others draw an arrow on the stem pointing the way the valve fails: up, away from the body, for FO and down for FC on the usual direct-acting body. Bars across the stem for FL and FI are rarer, so check the legend.

Shutdown and blowdown valves

An ESDV is often a ball or gate valve with a spring-return cylinder, a small S box for the solenoid on its air supply and FC under the body. A BDV looks similar but is normally closed, so it is often drawn filled, and it is marked FO because it has to open to blow the section down to flare. Both are on/off valves, not control valves.

Accessories on the stem

A small box on the stem below the dome is a positioner. Bubbles marked ZSO and ZSC beside a valve are limit switches that report open and closed, and some drawings write ZSH and ZSL for the same pair. An I/P converter is a Y bubble, such as FY, with I/P beside it: an electric signal goes in and a pneumatic signal comes out.

All 25 symbols

Handwheel operator P&ID symbol
Handwheel operator
HV
Manual valve operated by a handwheel.
Lever operator P&ID symbol
Lever operator
HV
Quarter-turn valve with a lever handle: small ball, plug and butterfly valves (typically 4" and below).
Gear operator P&ID symbol
Gear operator
HV
Manual valve with a gearbox, for large or high-pressure quarter-turn valves (ball, plug, butterfly) where a lever would be too hard to move.
Manual operator with position indicator P&ID symbol
Manual operator with position indicator
HV, ZI
Manual valve with a local open/closed position indicator, often required on firewater and deluge isolation valves so the position can be checked at a glance.
Diaphragm actuator (control valve) P&ID symbol
Diaphragm actuator (control valve)
FV, LV, PV, TV, FCV, LCV, PCV, TCV, HV
Pneumatic spring-diaphragm actuator: the typical modulating control valve.
Valve positioner P&ID symbol
Valve positioner
ZC, FY, LY, PY
Positioner on a control valve: compares the controller signal with stem position and drives the actuator.
Piston actuator, single acting (spring return) P&ID symbol
Piston actuator, single acting (spring return)
ESDV, SDV, XV
Air or hydraulic cylinder with spring return.
Piston actuator, double acting P&ID symbol
Piston actuator, double acting
XV, HV
Cylinder powered in both directions.
Electric motor actuator (MOV) P&ID symbol
Electric motor actuator (MOV)
MOV, XV, HV
Electric motor actuator: large isolation valves, pipeline and firewater valves, and tank valves where air is not available.
Solenoid actuator / solenoid valve (SOV) P&ID symbol
Solenoid actuator / solenoid valve (SOV)
SOV, XY, XV
Solenoid. On its own small valve it is a solenoid valve; on the air line of an ESDV actuator it is the SOV that vents the actuator to trip the valve.
Electro-hydraulic actuator P&ID symbol
Electro-hydraulic actuator
XV, ESDV, SDV
Self-contained actuator with its own electric pump and hydraulic cylinder.
Hydraulic actuator P&ID symbol
Hydraulic actuator
XV, SSV, SCSSV
Hydraulically powered cylinder, typical on wellhead valves (SSV/USV, wing valves) supplied from the wellhead HPU through the wellhead control panel.
Emergency shutdown valve (ESDV) P&ID symbol
Emergency shutdown valve (ESDV)
ESDV, SDV, XV, SSIV
Shutdown valve tripped by the ESD/PSD system.
Blowdown valve (BDV) P&ID symbol
Blowdown valve (BDV)
BDV
Depressuring valve. Closed in operation and opens on ESD or fire to blow inventory down to the flare (the usual API 521 fire-case guideline is 50 % of design pressure or 6.9 barg, whichever is lower, in about 15 min; other criteria are allowed).
Fail open (FO), arrow form P&ID symbol
Fail open (FO), arrow form
FO
On loss of air, power or signal the valve goes fully open.
Fail closed (FC), arrow form P&ID symbol
Fail closed (FC), arrow form
FC
On loss of air, power or signal the valve goes fully closed.
Fail locked (last position) (FL), arrow form P&ID symbol
Fail locked (last position) (FL), arrow form
FL
On loss of motive power the valve stays where it was.
Fail indeterminate (FI), arrow form P&ID symbol
Fail indeterminate (FI), arrow form
FI
The fail position is not defined: the valve may drift.
Fail open (FO), letter form P&ID symbol
Fail open (FO), letter form
FO
On loss of air, power or signal the valve goes fully open.
Fail closed (FC), letter form P&ID symbol
Fail closed (FC), letter form
FC
On loss of air, power or signal the valve goes fully closed.
Fail locked (last position) (FL), letter form P&ID symbol
Fail locked (last position) (FL), letter form
FL
On loss of motive power the valve stays where it was.
Fail indeterminate (FI), letter form P&ID symbol
Fail indeterminate (FI), letter form
FI
The fail position is not defined: the valve may drift.
Valve limit switches (ZSO / ZSC) P&ID symbol
Valve limit switches (ZSO / ZSC)
ZSO, ZSC, ZSH, ZSL, ZS
Open and closed position switches on an actuated valve, wired to the DCS/SIS for valve status and ESD verification.
I/P converter P&ID symbol
I/P converter
FY, LY, PY, TY
Converts the 4 to 20 mA controller output to a 0.2 to 1 barg air signal for the actuator.
Hand switch (HS) P&ID symbol
Hand switch (HS)
HS, HSS
Push-button or selector: local start/stop for a motor, open/close for an MOV, a manual ESD push-button (often HS with a solid bar = control room).

Download the legend sheet (SVG)Whole legend (SVG)

How each symbol is drawn

SymbolDrawn asTags
Handwheel operatorA valve body with a stem and a short horizontal bar on top (the handwheel), a "T".HV
Lever operatorA ball-valve body with a short stem and a lever drawn as a slanted line from the top of the stem.HV
Gear operatorA valve body with a small square box (gearbox) on its stem, and a handwheel shaft coming out of the side of the box.HV
Manual operator with position indicatorA handwheel valve with a small half-round dial with a pointer beside the stem, or a ZI bubble linked to the stem.HV, ZI
Diaphragm actuator (control valve)A bow-tie (often with a globe dot) with a stem and a dome-shaped head on top (a half circle sitting on a flat bar).FV, LV, PV, TV, FCV, LCV, PCV, TCV, HV
Valve positionerA control valve with a small box on the stem below the dome (the positioner), joined to the stem, with a signal line entering the box.ZC, FY, LY, PY
Piston actuator, single acting (spring return)A valve with a rectangle (the cylinder) on its stem; inside it a horizontal line (the piston) with a zig-zag spring above it.ESDV, SDV, XV
Piston actuator, double actingA rectangle (cylinder) on the valve stem with a piston line across the middle and a signal port into each end, with no spring.XV, HV
Electric motor actuator (MOV)A valve with a circle containing "M" on top of its stem.MOV, XV, HV
Solenoid actuator / solenoid valve (SOV)A square box containing "S" on the stem of a small valve, or a small S box on the air supply to a larger actuator.SOV, XY, XV
Electro-hydraulic actuatorA rectangle on the valve stem marked "EH".XV, ESDV, SDV
Hydraulic actuatorA cylinder rectangle on the stem with a piston line and "H", fed by a hydraulic signal line (a line with "L" marks).XV, SSV, SCSSV
Emergency shutdown valve (ESDV)A ball (or gate) valve with a spring-return cylinder on the stem, a small "S" box on its air supply, and "FC" written under the body.ESDV, SDV, XV, SSIV
Blowdown valve (BDV)A valve body drawn filled (normally closed) with a spring-return actuator, an "S" box, and "FO" under the body. Its outlet goes to flare.BDV
Fail open (FO), arrow formA control valve with an upward arrowhead drawn on the stem between body and actuator.FO
Fail closed (FC), arrow formA control valve with a downward arrowhead drawn on the stem between body and actuator.FC
Fail locked (last position) (FL), arrow formA control valve with two short horizontal bars across the stem between body and actuator.FL
Fail indeterminate (FI), arrow formA control valve with one short horizontal bar across the stem between body and actuator.FI
Fail open (FO), letter formThe letters "FO" written just below (sometimes beside) a valve body.FO
Fail closed (FC), letter formThe letters "FC" written just below (sometimes beside) a valve body.FC
Fail locked (last position) (FL), letter formThe letters "FL" written just below (sometimes beside) a valve body.FL
Fail indeterminate (FI), letter formThe letters "FI" written just below (sometimes beside) a valve body.FI
Valve limit switches (ZSO / ZSC)Two small bubbles marked ZSO and ZSC on either side of an actuated valve, joined to the stem by a short line.ZSO, ZSC, ZSH, ZSL, ZS
I/P converterA bubble with "Y" as the second letter (e.g. FY) with a small square beside it containing "I/P". An electric (dashed) signal goes in and a pneumatic (//) signal comes out.FY, LY, PY, TY
Hand switch (HS)A bubble with "HS" and a number, with an electric (dashed) signal line to the device it operates.HS, HSS

3D components for these symbols

Questions

What does FC mean on a P&ID valve?

Fail closed: the valve goes fully closed when it loses air, power or signal. It is typical for shutdown valves and feed or fuel valves. See fail closed, letter form and the arrow form.

What does a dome on top of a valve mean?

On most legends it is a pneumatic spring-diaphragm actuator, the usual sign of a modulating control valve. Its tag, such as FV, LV, PV or TV, names the loop it belongs to. See the diaphragm actuator symbol.

How is an emergency shutdown valve shown on a P&ID?

Often as a ball or gate valve with a spring-return cylinder on the stem, a small S box on its air supply and FC written under the body. Tags vary by company: ESDV, SDV and XV are all common. See the ESDV symbol.

What is the symbol for a motor-operated valve?

A valve with a circle containing M on top of its stem. It is often tagged MOV, but projects differ, so check the legend. See the motor actuator symbol.

What do ZSO and ZSC mean on a P&ID?

Position switch open and position switch closed: Z for position and S for switch, with O and C for the two ends of travel. The O and C are common practice rather than ISA 5.1 letters. They are drawn as two small bubbles beside an actuated valve. Some drawings write ZSH and ZSL for the same pair. See valve limit switches.