Flowmeter and field instrument P&ID symbols

A primary element is the part that touches the process: the orifice plate, the thermowell, the radar horn or the float. On a P&ID it is drawn on the line or vessel and joined to a tag bubble, such as FE, FT, LT or TT. The drawing on the pipe gives the measuring principle, and the bubble gives the variable and function.

30 symbols. Company legends vary, so the legend sheet of the drawing you are reading comes first.

How to read these symbols

Flow elements

Differential pressure meters change the pipe outline: an orifice plate is a bar with a gap between flanges, a venturi narrows and widens, and a flow nozzle curves inward. Other meters vary more between legends. This library draws them as an in-line box with a mark inside: M for magnetic, a bluff body and wavy trail for vortex, a rotor for turbine, a looped tube for Coriolis and two meshing rotors for positive displacement. An ultrasonic meter shows two transducers with a dashed diagonal path between them.

Level

A gauge glass is a narrow rectangle on two nozzles, and a magnetic gauge adds a column of indicator flaps. A displacer hangs inside an external cage. A dp level transmitter has two impulse lines, one to a low nozzle and one to a high nozzle. Radar is a cone on a top nozzle with wave arcs, and guided wave radar has a rod down into the liquid. A nuclear gauge has a source on one side of the vessel and a detector on the other.

Pressure and temperature

A PI or PT bubble on a thin impulse line is a pressure gauge or transmitter, often with a root valve. A PDT has two impulse lines across a filter, exchanger or column section. Here a thermowell is a U-shaped pocket dipping into the line, with TE, TT or TI above it. A capillary with × marks to a flat seal on the nozzle is a remote diaphragm seal.

Switches and analysers

Switch bubbles end in S and a limit, such as PSH or LSLL. An AT or AE bubble on a probe is an analyser, with the measured component written beside it, such as H2S, O2 or OIW. The letters follow ISA 5.1.

All 30 symbols

Orifice plate flow element with dp transmitter P&ID symbol
Orifice plate flow element with dp transmitter
FE, FT, FIT
Differential-pressure flow measurement.
Venturi tube P&ID symbol
Venturi tube
FE
Low-loss dp flow element for large water and gas lines and multiphase meters (venturi + gamma).
Flow nozzle P&ID symbol
Flow nozzle
FE
Dp flow element for high-velocity steam and gas.
Pitot tube P&ID symbol
Pitot tube
FE
Point-velocity flow probe.
Averaging pitot (multiport probe) P&ID symbol
Averaging pitot (multiport probe)
FE
Multi-port averaging pitot (Annubar type).
Electromagnetic flowmeter P&ID symbol
Electromagnetic flowmeter
FE, FT, FIT
Magnetic flowmeter for conductive liquids only: seawater, produced water, water injection, chemicals.
Vortex flowmeter P&ID symbol
Vortex flowmeter
FE, FT, FIT
Vortex-shedding meter for steam, gas and clean liquids: utilities, fuel gas, instrument air.
Turbine flowmeter P&ID symbol
Turbine flowmeter
FE, FT, FQ
Turbine meter for clean light liquids: fiscal oil metering (with a prover), diesel, chemicals.
Positive displacement flowmeter P&ID symbol
Positive displacement flowmeter
FE, FQ, FQI
Oval-gear or rotary PD meter for viscous liquids, chemical dosing and diesel transfer.
Ultrasonic flowmeter P&ID symbol
Ultrasonic flowmeter
FE, FT, FIT, FQ
Transit-time ultrasonic meter: fiscal gas metering (multipath), flare gas and large liquid lines.
Coriolis mass flowmeter P&ID symbol
Coriolis mass flowmeter
FE, FT, FIT, FQ
Coriolis mass meter: condensate, oil allocation, chemicals and LACT/fiscal liquid service.
Variable-area flowmeter (rotameter) P&ID symbol
Variable-area flowmeter (rotameter)
FI, FG
Local flow indicator for purge gas, small utilities, seal flush and chemical injection.
Thermowell with temperature element / transmitter P&ID symbol
Thermowell with temperature element / transmitter
TW, TE, TT, TIT
Temperature measurement: a thermowell (TW), an element (TE, an RTD or thermocouple) and a transmitter (TT).
Local temperature gauge P&ID symbol
Local temperature gauge
TI, TG
Bimetallic dial thermometer in a thermowell, read locally.
Local pressure gauge P&ID symbol
Local pressure gauge
PI, PG
Bourdon-tube dial gauge read locally: pump discharges, filters and vessels.
Pressure transmitter P&ID symbol
Pressure transmitter
PT, PIT
Electronic pressure transmitter feeding the DCS or SIS.
Differential pressure transmitter (PDT) P&ID symbol
Differential pressure transmitter (PDT)
PDT, PDIT, PDI
Differential pressure across equipment: filter or strainer fouling, scrubber dp, column flooding.
Pressure switch P&ID symbol
Pressure switch
PS, PSH, PSL, PSHH, PSLL
Pressure switch giving a discrete alarm or trip.
Level gauge glass P&ID symbol
Level gauge glass
LG
Reflex or transparent sight glass showing the level directly.
Magnetic level gauge P&ID symbol
Magnetic level gauge
LG, LI
Float-and-magnet level indicator on a bypass chamber, readable from a distance.
Displacer level transmitter P&ID symbol
Displacer level transmitter
LT, LIT
Buoyancy (displacer) level or interface transmitter.
Differential pressure level transmitter P&ID symbol
Differential pressure level transmitter
LT, LIT
Level from hydrostatic head: the most common level transmitter on separators and drums.
Guided wave radar level transmitter P&ID symbol
Guided wave radar level transmitter
LT, LIT
Guided wave radar: a pulse travels down the probe and reflects at the surface or interface.
Non-contact radar level transmitter P&ID symbol
Non-contact radar level transmitter
LT, LIT
Free-space radar for tanks and sumps: storage tanks, open drains and caissons.
Nuclear (gamma) level transmitter P&ID symbol
Nuclear (gamma) level transmitter
LT, RE
Gamma level or density measurement through the vessel wall: slug catchers, desanders, profilers in separators.
Vibrating fork level switch P&ID symbol
Vibrating fork level switch
LS, LSH, LSL, LSHH, LSLL
Point level switch for high or low alarms and trips, independent of the transmitter.
Float level switch P&ID symbol
Float level switch
LS, LSH, LSL
Mechanical float switch: sumps, drain drums, day tanks and lube-oil reservoirs.
Analyser (with sample probe) P&ID symbol
Analyser (with sample probe)
AT, AE, AIT, AI
Online analyser: water dew point, H2S, oxygen, oil-in-water, BS&W or water-cut.
Diaphragm (remote) seal with capillary P&ID symbol
Diaphragm (remote) seal with capillary
PT, LT
Remote seal protecting a transmitter from corrosive, viscous or hot process fluid.
Vibration element / transmitter on a machine P&ID symbol
Vibration element / transmitter on a machine
VE, VT, VXE, VYE, VI, VSHH
Machinery vibration sensor: proximity probes (shaft) or accelerometers (casing) on the bearings, wired to a proximitor junction box and a protection rack.

Download the legend sheet (SVG)Whole legend (SVG)

How each symbol is drawn

SymbolDrawn asTags
Orifice plate flow element with dp transmitterAn orifice plate between a flange pair on the line (a bar across the pipe with a gap in the middle for the bore), with two impulse lines from the flange taps up to an FT bubble.FE, FT, FIT
Venturi tubeThe line narrows through a short throat and widens again (converging and diverging lines either side of the pipe), with an FE bubble above.FE
Flow nozzleA flange pair with two curved lines inside the pipe converging downstream (the nozzle profile), and an FE bubble.FE
Pitot tubeA probe from an FE bubble into the pipe, bent into an L whose open end faces upstream.FE
Averaging pitot (multiport probe)A bar across the full pipe bore with several small holes (dots) on its upstream face, under an FE bubble.FE
Electromagnetic flowmeterAn in-line rectangle on the pipe with "M" inside, under an FT/FIT bubble.FE, FT, FIT
Vortex flowmeterAn in-line rectangle with a small triangle (the bluff body) and a wavy vortex trail behind it, under an FT bubble.FE, FT, FIT
Turbine flowmeterAn in-line rectangle with a small rotor (a hub with blades) inside, under an FT or FQ bubble.FE, FT, FQ
Positive displacement flowmeterAn in-line rectangle with two small touching ovals or circles (meshing rotors) inside, often with an FQ (totaliser) bubble.FE, FQ, FQI
Ultrasonic flowmeterTwo small transducers on opposite sides of the pipe, offset along it, with a dashed diagonal sound path between them, under an FT bubble.FE, FT, FIT, FQ
Coriolis mass flowmeterAn in-line box on the pipe with a looped (U-shaped) tube inside, under an FT bubble.FE, FT, FIT, FQ
Variable-area flowmeter (rotameter)A vertical tapered tube, wider at the top, with a small float inside; the flow enters at the bottom and leaves at the top.FI, FG
Thermowell with temperature element / transmitterA U-shaped pocket dipping into the line (the thermowell), with a line up to a TT or TE bubble.TW, TE, TT, TIT
Local temperature gaugeA thermowell (U-shaped pocket in the line) with a TI bubble on it.TI, TG
Local pressure gaugeA PI (or PG) bubble on a thin impulse line from the pipe, often with a small root or isolation valve on the impulse line.PI, PG
Pressure transmitterA PT (or PIT) bubble on a thin impulse line from the pipe or vessel, with an electric (dashed) signal leaving to the DCS.PT, PIT
Differential pressure transmitter (PDT)A PDT bubble with two impulse lines: one to each side of a filter, strainer, exchanger or column section.PDT, PDIT, PDI
Pressure switchA bubble with PSH, PSL, PSHH or PSLL on an impulse line from the process.PS, PSH, PSL, PSHH, PSLL
Level gauge glassA tall narrow rectangle beside the vessel, joined to it by two horizontal nozzles (top and bottom), with an LG bubble.LG
Magnetic level gaugeA chamber beside the vessel on two nozzles, with a float inside and a column of indicator flaps (half-filled marks) on its face, and an LG bubble.LG, LI
Displacer level transmitterAn external cage beside the vessel on two nozzles, with a long slender displacer hanging inside from a torque tube at the top, and an LT bubble.LT, LIT
Differential pressure level transmitterAn LT bubble with two impulse lines to the vessel: one from a low nozzle (high side) and one from a high nozzle (low side). Remote seals are drawn as capillaries (line with × marks).LT, LIT
Guided wave radar level transmitterAn LT bubble on a vessel-top (or chamber-top) nozzle, with a straight rod or cable probe running down into the liquid.LT, LIT
Non-contact radar level transmitterAn LT bubble on a vessel-top nozzle, with a cone (horn antenna) pointing down and wave arcs (unguided signal) towards the liquid.LT, LIT
Nuclear (gamma) level transmitterA source holder (small box) on one side of the vessel and a detector rod on the other, joined by a wavy (radiation) line across the vessel, with an LT bubble on the detector.LT, RE
Vibrating fork level switchA short side nozzle into the vessel with two small prongs (the fork) inside, and an LS bubble (LSH, LSHH…) outside.LS, LSH, LSL, LSHH, LSLL
Float level switchA float (circle) on a short arm inside the vessel, pivoted at the wall, with an LS bubble outside.LS, LSH, LSL
Analyser (with sample probe)An AT (or AE) bubble linked to a probe that dips into the line, with the measured component written beside the bubble (O2, H2S, H2O, OIW, BS&W, CO2…).AT, AE, AIT, AI
Diaphragm (remote) seal with capillaryA small flat seal on the pipe or vessel nozzle (a short rectangle with a curved diaphragm line), joined to a transmitter bubble by a capillary (a line with × marks).PT, LT
Vibration element / transmitter on a machineA VE (or VT) bubble joined by a short line to a small square or dot on the outline of a motor, pump, compressor or bearing. Often in pairs (A / B or X / Y), one per bearing or per axis, with VI / VA / VSHH functions downstream.VE, VT, VXE, VYE, VI, VSHH

3D components for these symbols

Questions

What is the symbol for an orifice plate on a P&ID?

An orifice plate between a flange pair on the line, drawn as a bar across the pipe with a gap for the bore, with two impulse lines from the flange taps up to an FT bubble. See the orifice plate symbol.

How do you tell a flow orifice from a restriction orifice?

Both are a plate between flange bars. A flow-measuring orifice has impulse lines from the taps to a transmitter. A restriction orifice has no taps and is labelled RO or FO.

What does FE mean on a P&ID?

Flow element: F for flow, E for the primary element, the part in the pipe that senses the flow. It is usually paired with an FT, the flow transmitter.

What does a thermowell look like on a P&ID?

In this library, a U-shaped pocket dipping into the line, with a line up to a TE, TT or TI bubble. Some legends draw a short line into the pipe with a dot. The pocket is tagged TW. See the thermowell symbol.

How is a radar level transmitter shown on a P&ID?

A non-contact radar is an LT bubble on a vessel-top nozzle with a cone pointing down and wave arcs towards the liquid. A guided wave radar has a straight rod or cable running down into the liquid instead.