Fire and gas P&ID symbols
Fire and gas symbols appear on F&G layout drawings and on firewater P&IDs. Detectors are small shapes with a letter code such as GD, FD or HD, and their shapes differ widely between companies. Firewater items follow the piping: the fire pumps, the ring main, the deluge valves and the nozzles or sprinklers they feed.
24 symbols. Company legends vary, so the legend sheet of the drawing you are reading comes first.
How to read these symbols
Detectors
GD is a point gas detector, often with the gas noted, such as HC or H2S. OGD is an open-path detector, drawn as a transmitter and receiver joined by a dashed beam. FD is a flame detector, often with a dashed cone for its field of view. HD is a heat detector and SD a smoke detector. Some legends draw detectors as circles, others as triangles or hexagons.
Alarms and call points
Company F&G legends often use their own shapes or letters for these. This library draws a manual call point as a square with a filled circle inside. A beacon is a circle with an X and short rays, a sounder a dome on a base line and a PA loudspeaker a trumpet shape, after the IEC 60617 lamp, bell and loudspeaker symbols.
Firewater
A deluge valve is drawn normally closed on the firewater supply with a trip actuator on top. It feeds open spray nozzles, drawn here as small triangles with spray lines. A sprinkler is a closed head: a small filled bulb with a deflector bar. A deluge zone sprays from all its nozzles at once, while each sprinkler head opens on its own in the heat of a fire. Water spray systems are covered by NFPA 15 and fire pumps by NFPA 20.
Equipment and signs
Extinguishers are marked with the agent, such as DP for dry powder or CO2. Layout drawings often use the ISO 7010 safety signs for extinguishers and safety showers instead of process-style symbols.
All 24 symbols
Download the legend sheet (SVG)Whole legend (SVG)
How each symbol is drawn
| Symbol | Drawn as | Tags |
|---|---|---|
| Gas detector (point, flammable) | A small bubble (or hexagon or triangle, by legend) with "GD", often with the gas noted (HC, CH4) and the zone or voting group beside it. | GD, GT, AT, AE |
| Toxic gas detector (H2S, CO) | A detector bubble marked with the toxic gas, usually "H2S" (or "CO"). | GD, TD, AT |
| Open-path (line-of-sight) gas detector | A transmitter box and a receiver box joined by a dashed beam line, marked OGD or Tx/Rx. | OGD, OPGD, LOS |
| Acoustic (ultrasonic) gas leak detector | A detector bubble with "UGD" and curved sound arcs beside it. | UGD, AGD, UGLD |
| Flame detector | A detector bubble with "FD" and a dashed cone showing its field of view. | FD, BS, IR3, BE |
| Heat detector | A detector bubble with "HD" (sometimes a TSH bubble, or a square in building legends). | HD, TS, TSH |
| Smoke detector | A detector bubble with "SD". | SD |
| Manual call point (MAC) | A square with a smaller filled circle inside (the break-glass button), sometimes marked MAC or MCP. | MAC, MCP, HS |
| Alarm beacon (visual) | A circle with an X inside (the IEC lamp symbol) and short rays around it, often with the colour noted (red, yellow, blue). | XL, BCN |
| Alarm sounder / bell | A half-circle dome sitting on a flat base line (the IEC bell or sounder), with its connection below. | XA, SNDR |
| PA/GA loudspeaker (horn) | A small rectangle with a flared trumpet (trapezoid) opening out of it, the IEC loudspeaker or horn. | LS, PA |
| Deluge valve | A valve drawn filled (normally closed) on the firewater supply with a trip actuator on top (often a solenoid "S" box or hydraulic latch), and "DV" or the deluge zone written beside it. Open (dry) pipework leads to the nozzles downstream. | DV, XV |
| Sprinkler head (closed) | A small drop from the pipe ending in a closed head: a small filled circle (the glass bulb) with a short deflector bar. | SPK |
| Deluge (open) spray nozzle | A small drop from the pipe ending in an open nozzle (a small triangle), with dashed spray lines fanning out. | NZ |
| Water mist nozzle / system | A nozzle on a small-bore line with a fine dotted spray cone, often inside an enclosure outline and marked "WM". | WM |
| Fire hydrant | A pillar on the firewater main with a cap on top and two hose outlets on the sides. | HYD, FH |
| Fire monitor | A riser from the firewater main with a swivel joint (circle) on top and a nozzle barrel angled out of it, sometimes with an arc showing its sweep. | FM, MON |
| Fire hose reel | A drum (two concentric circles) fed from the firewater line through a valve, with a hose ending in a nozzle. | HR |
| Portable fire extinguisher | A canister outline with a handle and short hose, marked with the agent: DP (dry powder), CO2, F (foam) or W (water). | EXT, FE |
| Firewater pump (diesel driven) | A pump (centrifugal circle, or a vertical turbine pump into a caisson) driven by a "DE" diesel engine box, discharging into the firewater ring main. | P, FWP |
| Foam system (concentrate tank and proportioner) | A small vertical tank of foam concentrate (marked AFFF or F) joined to an in-line proportioner (a venturi-like body) on the firewater line. | C, X |
| CO2 / inert gas extinguishing system | A bank of cylinders on a manifold with a release valve, piped to discharge nozzles inside an enclosure outline, marked CO2, IG-541 or N2. | X, CO2 |
| Safety shower and eyewash | A shower head (an inverted cone) on a pipe stand, often with a small eyewash bowl on the side, fed from potable water. | SS, EW |
| Fusible plug loop | An instrument-air (pneumatic //) loop with small fusible plug elements (small filled squares marked FP) placed around the wellhead or equipment. | FP, TSE |
3D components for these symbols
Questions
What is the symbol for a gas detector on a P&ID?
A small bubble, hexagon or triangle, depending on the legend, marked GD, often with the gas noted and the zone or voting group beside it. On P&IDs it may be an ISA bubble marked AT or AE with LEL. See the gas detector symbol.
What is the difference between a deluge nozzle and a sprinkler symbol?
A deluge nozzle is open: here a small triangle with dashed spray lines, which sprays when the deluge valve opens. A sprinkler is closed: a small filled bulb with a deflector, which opens by itself in the heat of a fire.
What does MAC mean on a fire and gas drawing?
Manual alarm call point, also written MCP: a break-glass device for raising the alarm by hand. In this library it is a square with a smaller filled circle inside. See the manual call point symbol.
How is a deluge valve shown on a P&ID?
As a valve drawn filled, normally closed, on the firewater supply, with a trip actuator on top and DV or the deluge zone written beside it. Open dry pipe runs downstream to the nozzles. See the deluge valve symbol.
What does OGD mean on a fire and gas drawing?
Open-path gas detector: a transmitter and receiver that measure gas along the beam between them rather than at one point. See the open-path gas detector symbol.
Other symbol categories
- Valves 23
- Check valves 6
- Relief, regulators and safety devices 9
- Actuators, operators and valve accessories 25
- Piping fittings and specials 37
- Lines and signals 16
- Connectors, boundaries and annotations 11
- Instrument bubbles and functions (ISA 5.1) 14
- Primary elements and field instruments 30
- Vessels, columns and tanks 13
- Heat transfer equipment 12
- Pumps 9
- Compressors, blowers and drivers 15
- Filters, separators and mixers 10
- Flare, wellhead, pipeline and packages 16
- Electrical (single-line) 23