Electrical single-line diagram symbols
The electrical single-line diagram (SLD) is a separate drawing from the P&ID. It draws a three-phase system as one line, from the generators and transformers through the switchboards to each motor or feeder. The shapes here follow IEC 60617, and ANSI legends draw some of them differently. A motor or VFD can appear on both drawings, joined by its tag.
23 symbols.
How to read these symbols
Switching devices
A switch is a lead with a diagonal blade, and the mark on the fixed contact names it: a small × for a circuit breaker, a short bar for a disconnector and a half-circle for a contactor. A rectangle with the line running through it is a fuse. ANSI single-line diagrams usually draw a breaker as a square box instead.
Machines and transformers
A circle with M is a motor and a circle with G a generator. Two overlapping circles are a two-winding transformer and three in a triangle a three-winding one, with the rating and vector group beside them. Smaller overlapping circles on a fused tap are a voltage transformer, and a small circle around the conductor is a current transformer.
Boards, drives and backup power
A thick horizontal line with feeders dropping from it is a busbar. A dashed frame around a busbar and its breakers is a switchboard or MCC. A square split by a diagonal with ~ in each half is a VFD. A UPS is a rectifier, a battery and an inverter in series, often with a static bypass.
Earthing and protection
Three horizontal lines getting shorter downward are an earth. A rectangle between a transformer or generator neutral and earth is a neutral earthing resistor. A rectangle with a downward arrow to earth is a surge arrester. Protection relays carry an ANSI device number from IEEE C37.2, such as 50/51 for overcurrent or 87 for differential.
All 23 symbols
Download the legend sheet (SVG)Whole legend (SVG)
How each symbol is drawn
| Symbol | Drawn as | Tags |
|---|---|---|
| Two-winding transformer | Two overlapping circles (one per winding) on the single-line diagram, with the rating and vector group written beside them. | TR, T, TX |
| Three-winding transformer | Three overlapping circles in a triangle: one primary on top, two secondaries below. | TR, T |
| Circuit breaker | A switch (a lead with a diagonal blade) with a small × on the fixed contact. | CB, Q |
| Disconnector (isolator) | A switch blade with a short bar across the fixed contact. | DS, Q |
| Earthing switch | A disconnector blade whose lower side goes straight to an earth symbol, branching off a main circuit. | ES |
| Fuse | A small rectangle with the conductor line passing straight through it. | F, FU |
| Contactor | A switch blade with a small half-circle on the fixed contact. | K, KM |
| Motor (electrical) | A circle containing "M" and "3~" at the end of a feeder. | M, PM |
| Generator | A circle containing "G" (often with a "~"), at the top of a feeder to the switchboard. | G |
| Variable frequency drive (VFD) | A square split by a diagonal, with "~" in both halves (an AC/AC converter), feeding a motor. | VFD, VSD, U |
| Uninterruptible power supply (UPS) | A rectifier box (~/=) and an inverter box (=/~) in series with a battery between them, often inside a dashed frame with a static bypass. | UPS |
| Battery | Pairs of parallel plates: a long thin line (positive) and a short thick line (negative), repeated. | BAT, G |
| Busbar | A thick horizontal line with feeders dropping from it, labelled with the board name and voltage. | BB |
| Current transformer (CT) | A small circle around the conductor line, with secondary leads to a meter or relay. | CT, T |
| Voltage transformer (VT) | Two small overlapping circles (like a power transformer, but smaller), on a fused tap from the busbar, with the secondary earthed. | VT, PT |
| Surge arrester | A rectangle with a downward arrow inside, connected between the conductor and earth. | SA, F |
| Earth (ground) | A vertical lead ending in three horizontal lines that get shorter downward. | E, PE |
| Capacitor | Two short parallel plates with a lead on each side. | C |
| Neutral earthing resistor (NER) | A rectangle (resistor) between a transformer or generator neutral point and an earth symbol. | NER, R |
| Switchboard / MCC | A dashed frame around a busbar with an incoming breaker and outgoing feeders (breakers or contactors), labelled with the board tag and voltage. | SWB, SWG, MCC |
| Junction box | A small square marked "JB" with cables entering it. | JB |
| Local control station (LCS) | A small box beside a motor marked "LCS", with start/stop push-buttons (small circles) or HS bubbles, and a dashed signal line to the MCC. | LCS, HS |
| Protection relay (ANSI device number) | A small circle or box with an ANSI device number (e.g. 50/51 overcurrent, 87 differential, 27 undervoltage), joined to a CT or VT by a dashed line. | R |
3D components for these symbols
Questions
What is a single-line diagram?
A drawing of an electrical power system with each three-phase circuit shown as one line. It shows the sources, transformers, switchboards, breakers and loads, with their ratings, but not the control wiring.
What is the symbol for a circuit breaker on a single-line diagram?
In IEC 60617 style, a switch blade with a small × on the fixed contact. ANSI single-line diagrams usually draw a square box, and ANSI schematics may show an arc across the contacts. See the circuit breaker symbol.
How do you tell a circuit breaker from a disconnector?
Look at the fixed contact. A circuit breaker has a small × there and can interrupt fault current. A disconnector has a short bar there and is opened off load, to isolate a circuit for work.
What is the symbol for a transformer on a single-line diagram?
Two overlapping circles, one for each winding, with the rating and vector group written beside them. A three-winding transformer has three circles in a triangle. See the two-winding transformer symbol.
What do 50/51 and 87 mean on a single-line diagram?
They are ANSI device numbers from IEEE C37.2, written on protection relays. 50 is instantaneous overcurrent, 51 AC time overcurrent, 87 differential and 27 undervoltage. A combined number such as 50/51 is one relay with both functions. See the protection relay symbol.
Other symbol categories
- Valves 23
- Check valves 6
- Relief, regulators and safety devices 9
- Actuators, operators and valve accessories 25
- Piping fittings and specials 37
- Lines and signals 16
- Connectors, boundaries and annotations 11
- Instrument bubbles and functions (ISA 5.1) 14
- Primary elements and field instruments 30
- Vessels, columns and tanks 13
- Heat transfer equipment 12
- Pumps 9
- Compressors, blowers and drivers 15
- Filters, separators and mixers 10
- Flare, wellhead, pipeline and packages 16
- Fire & gas and fire protection 24