Piping fitting symbols on a P&ID

Fittings sit in the line between valves and equipment. They are drawn small and are easy to miss on a busy sheet. Many are built from flange bars: two short bars across the pipe are a flanged joint, and whatever sits between them names the fitting. Marks drawn along a line, such as insulation, tracing and slope, are kept in this group too.

37 symbols. Company legends vary, so the legend sheet of the drawing you are reading comes first.

How to read these symbols

Reducers

A reducer is a trapezoid in the line. A symmetric one is concentric. A flat top or flat bottom edge makes it eccentric, often marked FOT or FOB. Flat on top is usual on horizontal pump suctions, because it stops a vapour pocket forming.

Blinds, spades and spacers

A spectacle blind is a figure-8 between two flange bars, and the half on the pipe gives its state: a filled blank on the line means closed, an open ring on the line means open. A spade is a single blank with a handle tab, and a spacer is a single ring. Some legends draw the figure-8 beside the flanges on a short stem. These blanks are covered by ASME B16.48.

Strainers and other in-line items

A Y-strainer is a leg slanting off the pipe at about 45 degrees with a dashed screen inside. A basket strainer hangs below the line with a dashed U inside. A temporary cone strainer is a dashed triangle just downstream of a flange pair. Steam traps and sight glasses vary between legends. This library draws a steam trap as a small circle with T inside and a sight glass as two concentric circles.

Marks along the line

Many drawings only write insulation and tracing codes in the line number or beside the line. Where they are drawn, this library uses thin dashed lines on both sides of the pipe for insulation, a thin zig-zag marked ET beside it for electric tracing and a dashed tracer marked ST for steam tracing. A bar with a piping class code on each side is a specification break. Where two lines cross, a gap or a hop means they do not connect, and a dot at a tee means they do.

All 37 symbols

Concentric reducer P&ID symbol
Concentric reducer
Size change on vertical lines, or where the centreline must stay put.
Eccentric reducer, flat on top (FOT) P&ID symbol
Eccentric reducer, flat on top (FOT)
Eccentric reducer with the flat side up.
Eccentric reducer, flat on bottom (FOB) P&ID symbol
Eccentric reducer, flat on bottom (FOB)
Eccentric reducer with the flat side down.
Spectacle blind, open (spacer in line) P&ID symbol
Spectacle blind, open (spacer in line)
SB
Spectacle blind in the open position: flow passes through the ring.
Spectacle blind, closed (blank in line) P&ID symbol
Spectacle blind, closed (blank in line)
SB
Spectacle blind in the closed position: positive isolation, nothing passes.
Spectacle blind, offset figure-8 (drawn beside the flanges) P&ID symbol
Spectacle blind, offset figure-8 (drawn beside the flanges)
SB
Spectacle blind between the flanges, drawn beside the line so the pipe stays unbroken.
Spade (line blank) P&ID symbol
Spade (line blank)
Removable paddle blank: positive isolation for large sizes, where a spectacle blind would be too heavy.
Spacer (ring spacer) P&ID symbol
Spacer (ring spacer)
The ring that is fitted in place of a spade when the line is in service.
Blind flange P&ID symbol
Blind flange
Bolted blind on the end of a line or a spare nozzle.
Flanged joint P&ID symbol
Flanged joint
Bolted flange connection, usually shown only where it matters: equipment nozzles, spool breaks, spec breaks and maintenance breaks.
Pipe cap P&ID symbol
Pipe cap
Welded or threaded cap closing a pipe end: dead legs, future connections, header ends.
Union P&ID symbol
Union
Threaded union, used on small-bore lines (instrument air, chemical injection, tubing) to allow disconnection.
Flexible hose P&ID symbol
Flexible hose
FH
Flexible hose or hose assembly: loading hoses, temporary connections, vibrating equipment hook-ups, and HPU or chemical hoses.
Expansion joint (bellows) P&ID symbol
Expansion joint (bellows)
EJ
Metallic or rubber bellows that absorbs thermal movement or vibration: exhaust ducts, seawater pump discharges and flare headers.
Y-strainer P&ID symbol
Y-strainer
S, STR
Permanent in-line strainer protecting pumps, control valves and meters.
Basket (T-type) strainer P&ID symbol
Basket (T-type) strainer
S, STR
Large-capacity strainer for pump suctions and seawater systems.
Temporary (cone) strainer P&ID symbol
Temporary (cone) strainer
TS
Start-up strainer fitted between flanges for commissioning and removed afterwards.
Steam trap P&ID symbol
Steam trap
ST, TR
Lets condensate out of a steam line or tracer while holding steam back.
Sight glass (sight flow indicator) P&ID symbol
Sight glass (sight flow indicator)
SG, FG
In-line window to see that liquid is flowing: pump seal flush, lube oil, chemical injection.
Restriction orifice P&ID symbol
Restriction orifice
RO, FO
Fixed plate that limits flow: after blowdown valves, on minimum-flow lines and on purge connections.
Insulating joint (monolithic) P&ID symbol
Insulating joint (monolithic)
IJ
Electrically isolates a pipeline (cathodic protection) from the plant.
Drain funnel (tundish) P&ID symbol
Drain funnel (tundish)
OD, TD
Open drain hub with a visible air break.
Hose connection P&ID symbol
Hose connection
HC, UC
Utility hose connection (utility station: air, nitrogen, water or steam) or a flushing / steam-out connection.
Vent with cap P&ID symbol
Vent with cap
VT
High-point vent for hydrotest and commissioning: valve plus cap or blind.
Drain with plug P&ID symbol
Drain with plug
DR
Low-point drain for hydrotest and maintenance: valve plus plug.
Sample connection P&ID symbol
Sample connection
SC, SP, AX
Manual sample point for lab analysis (oil-in-water, BS&W, H2S, glycol).
Piping specification break P&ID symbol
Piping specification break
Where the piping class (material and pressure rating) changes, usually at a valve or a flange.
Insulation mark P&ID symbol
Insulation mark
The line is insulated (heat conservation, personnel protection or cold).
Electric heat tracing mark P&ID symbol
Electric heat tracing mark
ET, EHT
Electrically traced line to stop freezing, waxing or hydrates.
Steam tracing mark P&ID symbol
Steam tracing mark
ST
Steam- or hot-oil-traced line.
Slope (fall) mark P&ID symbol
Slope (fall) mark
The line must fall continuously in the arrow direction: drains, flare headers and relief lines (no pockets).
Flow direction arrow P&ID symbol
Flow direction arrow
Direction of normal flow in the line.
Line crossing (no connection) P&ID symbol
Line crossing (no connection)
The lines cross on paper only and are not connected.
Line junction (tee) P&ID symbol
Line junction (tee)
Branch connection: a tee, or a welded branch fitting (olet).
Injection quill / point P&ID symbol
Injection quill / point
IP, CI
Chemical injection point: corrosion inhibitor, scale inhibitor, methanol, demulsifier, biocide.
Corrosion probe / coupon P&ID symbol
Corrosion probe / coupon
CP, CC, CE
Corrosion monitoring point: an ER/LPR probe or a weight-loss coupon in a high-pressure access fitting.
Vent to atmosphere (gooseneck) P&ID symbol
Vent to atmosphere (gooseneck)
VA, TV
Open vent to a safe location: instrument-air and nitrogen relief, tank vents and utility PSV outlets.

Download the legend sheet (SVG)Whole legend (SVG)

How each symbol is drawn

SymbolDrawn asTags
Concentric reducerA symmetric trapezoid in the line: tall at the large end and short at the small end, with both pipe centrelines in line.
Eccentric reducer, flat on top (FOT)A trapezoid with a flat top edge and a sloped bottom edge, so the two pipe centrelines are offset. Often marked "FOT".
Eccentric reducer, flat on bottom (FOB)A trapezoid with a flat bottom edge and a sloped top, centrelines offset. Often marked "FOB".
Spectacle blind, open (spacer in line)A figure-8 between two flange bars: the open ring sits on the pipe, and the solid (filled) blank sits off the line.SB
Spectacle blind, closed (blank in line)A figure-8 between two flange bars: the solid (filled) blank sits on the pipe, and the open ring is off the line.SB
Spectacle blind, offset figure-8 (drawn beside the flanges)A flange pair (two short bars) on the line, with a figure-8 drawn off to one side and joined to the flanges by a short stem. The circle next to the stem is the half installed in the line; the far circle is the spare half. The blank half may be filled, hatched or drawn as concentric circles; the ring half is a plain open circle.SB
Spade (line blank)A single solid blank between two flange bars with a short handle tab sticking out, and no ring.
Spacer (ring spacer)A single open ring between two flange bars with a short handle tab, and no blank.
Blind flangeThe pipe ends at a flange bar followed by a thicker solid bar.
Flanged jointTwo short parallel bars across the pipe, close together.
Pipe capThe pipe ends in a small half-round (a "D").
UnionTwo short bars across the pipe with a shorter third bar between them.
Flexible hoseA wavy line between two short end bars.FH
Expansion joint (bellows)A zig-zag bellows drawn above and below the pipe between two flange bars.EJ
Y-strainerA leg slanting down from the pipe at about 45°, with a dashed screen line inside and a cap at its end.S, STR
Basket (T-type) strainerA rectangle hanging below the line with a cover bar on top and a dashed U (the basket) inside.S, STR
Temporary (cone) strainerA dashed cone (triangle) pointing downstream inside the pipe, just downstream of a flange pair.TS
Steam trapA small circle on the line with "T" inside.ST, TR
Sight glass (sight flow indicator)Two concentric circles on the line (a viewing window).SG, FG
Restriction orificeAn orifice plate between two flange bars (a bar across the pipe with a gap in the middle), labelled "RO" or with an FO bubble.RO, FO
Insulating joint (monolithic)A short rectangle on the line with diagonal hatching inside, sometimes labelled "IJ".IJ
Drain funnel (tundish)A drain line ending in the open, just above a V-shaped funnel that leads down to the open drain.OD, TD
Hose connectionA small isolation valve on a branch that ends in a coupling (a short block with ridges), often marked "HC".HC, UC
Vent with capA short branch rising from the line with a small isolation valve and a cap (half-round) on top.VT
Drain with plugA short branch going down from the line with a small isolation valve and a solid plug (filled square) at the end.DR
Sample connectionA small branch from the line with a needle or isolation valve, ending in an open end over a small bottle; sometimes a box labelled "SC" or a sample cooler.SC, SP, AX
Piping specification breakA short bar across the line with the two piping class codes written on either side of it (e.g. A1A | D6A).
Insulation markA process line with thin dashed lines running parallel above and below it over the insulated length.
Electric heat tracing markA process line with a thin zig-zag (resistor-like) line running beside it, marked "ET".ET, EHT
Steam tracing markA process line with a thin dashed tracer line beside it, marked "ST", usually ending at a steam trap.ST
Slope (fall) markThe word "SLOPE" or a ratio (e.g. 1:100) with an arrow along the line pointing downhill.
Flow direction arrowA solid arrowhead on the line.
Line crossing (no connection)Two lines crossing, with one broken (a small gap either side of the other line), or with a small hop (semicircle) over it.
Line junction (tee)A branch line meeting a run line in a T, with a solid dot at the junction.
Injection quill / pointA small branch entering the pipe (often after a check valve), with its end bent inside the pipe and pointing downstream.IP, CI
Corrosion probe / couponA short access fitting on top of the line with a small box or bubble marked "CP" (probe) or "CC" (coupon), and a probe tip into the flow.CP, CC, CE
Vent to atmosphere (gooseneck)A line rising and turning back down at the top (a gooseneck or bent open end), sometimes with "ATM" written beside it.VA, TV

3D components for these symbols

Questions

What is the symbol for a spectacle blind?

A figure-8 between two flange bars: one half a solid blank, the other an open ring. The half sitting on the pipe tells you whether the line is blinded or open.

How do you tell a concentric reducer from an eccentric reducer?

A concentric reducer is a symmetric trapezoid with both centrelines in line. An eccentric reducer has one flat edge, either flat on top or flat on bottom, so the centrelines are offset.

What does a Y-strainer look like on a P&ID?

A leg slanting down from the pipe at about 45 degrees, with a dashed screen line inside and a cap at its end. It is often tagged S or STR. See the Y-strainer symbol.

What does a restriction orifice look like on a P&ID?

An orifice plate between two flange bars, drawn as a bar across the pipe with a gap in the middle, labelled RO or with an FO bubble. A flow-measuring orifice looks similar but has impulse lines to a transmitter. Compare the restriction orifice with the orifice plate flow element.

How is a piping specification break shown?

Usually as a short bar across the line with the two piping class codes written on either side of it, for example A1A and D6A. See the spec break symbol.

Other symbol categories