API RP 14C
Safety systems for offshore production facilities
API RP 14C explained: safety analysis of offshore production facilities, two levels of protection, PSH, LSL and SDV device codes, and the SAFE chart.
Scope
API RP 14C is a recommended practice for the analysis, design, installation and testing of the surface safety systems on offshore production facilities. It takes each process component in turn, such as a wellhead, a separator, a pump or a compressor, works out what can go wrong with it, and sets out the safety devices that should detect and stop it.
It is widely used for the process shutdown design of platforms in the US Gulf of Mexico, where the US offshore regulations in 30 CFR 250 incorporate it by reference, and it is widely used elsewhere. The regulations name an earlier edition, so check which one applies. The method is also used in ISO 10418, the international standard for the basic surface process safety systems of offshore installations. The current ISO 10418 refers to the RP 14C analysis tables instead of reproducing them.
RP 14C covers the process safety devices and the shutdown logic they feed. It does not cover the design of the process itself, fire and gas detection in depth, or the safety instrumented system lifecycle, which follows IEC 61511. Relief sizing follows API 520 and API 521.
How the safety analysis works
- 1
Split the process into components
The facility is broken into standard components: wellheads and flowlines, headers, pressure vessels, atmospheric vessels, fired components, pumps, compressors, pipelines and heat exchangers.
- 2
Safety analysis table (SAT)
For each component type a table lists the undesirable events, such as overpressure, leak, liquid overflow or gas blowby, with their causes and the conditions a sensor can detect.
- 3
Safety analysis checklist (SAC)
A checklist then names the protective devices each component needs. Where a device can be left out, it records the reason, for example that protection is given by another component upstream.
- 4
SAFE chart
The safety analysis function evaluation chart lists every sensing device and the shutdown or other action it causes. It ties the analysis to the cause and effect logic of the control system.
- 5
Test
The practice also covers how often and how the safety devices are tested once the facility is running.
Two levels of protection
RP 14C asks for two levels of protection against each undesirable event, independent of and in addition to the control devices used in normal operation. The primary level should be the highest order of protection that suits the case, and the secondary level the next one. A common example is a pressure vessel with a high-pressure sensor (PSH) that shuts in the inflow as the primary level, and a relief valve (PSV) as the secondary level.
In general the two levels should be given by functionally different devices, so that one fault cannot defeat both. Emergency support systems, such as the ESD system, fire detection and gas detection, add a further layer above them.
Common safety device designations
RP 14C gives safety devices short letter codes that look like ISA instrument tags. The second letter S means safety, so a PSH is a pressure safety high device, not a pressure switch in a control loop.
| Code | Device | Typical use |
|---|---|---|
| PSH / PSL | Pressure safety high / low | Shut in a vessel on high pressure, or on low pressure that can mean a leak |
| PSV | Pressure safety valve | Relieve overpressure, usually the secondary level of protection |
| PSE | Pressure safety element | A rupture disc |
| LSH / LSL | Level safety high / low | Stop overflow into the gas outlet, or gas blowby through the liquid outlet |
| TSH / TSL | Temperature safety high / low | Protect fired heaters, compressors and exchangers |
| FSH / FSL | Flow safety high / low | Detect abnormal flow in lines and pumps |
| FSV | Flow safety valve | A check valve that stops backflow |
| ASH | Analyser safety high | Combustible gas detection |
| BSL | Burner safety low | Flame failure detection on a fired component |
| SDV / SSV / USV / BDV | Shutdown, surface safety, underwater safety and blowdown valves | The final elements that isolate or depressure |
A commonly quoted selection, as used in earlier editions of RP 14C. It is not a copy of the standard's table. Check the current edition for the full list and its symbols.
Key concepts
- Undesirable events
- The analysis looks for events that can lead to a release or a fire, such as overpressure, leak, liquid overflow, gas blowby, underpressure and excess temperature. Each component type is checked against the ones that apply to it.
- Process component
- The analysis is done on standard building blocks, not on the whole plant at once. This makes the result repeatable and easy to check, and the same tables can be reused on any facility.
- Surface safety valve
- The SSV is the actuated valve on the wellhead that shuts in the well. On a subsea well the same role is taken by the underwater safety valve (USV). Downhole, a subsurface safety valve gives further protection.
- Emergency support systems
- The ESD system, fire detection, combustible gas detection, the containment system and the subsurface safety valves are the support systems. They act when the process safety devices are not enough or when the event is outside one component.
- Bypassing
- Some devices must be bypassed during start-up, such as a low-pressure sensor on an empty vessel. The practice expects bypasses to be controlled, visible to the operator and removed automatically or under procedure.
- Relationship to SIS design
- RP 14C sets which devices are needed. Many operators now treat the shutdown functions it calls for as safety instrumented functions and design them to IEC 61511, with a SIL target where one is needed.
Questions
What is API RP 14C?
It is API's recommended practice for the analysis, design, installation and testing of safety systems on offshore production facilities. It analyses each process component in turn and sets out the safety devices needed to detect and stop abnormal conditions. The current edition is the 8th, published in February 2017, with an errata of May 2018.
What is a SAFE chart?
SAFE stands for safety analysis function evaluation. The chart lists each process component, the safety devices on it and the action each device causes, such as closing a shutdown valve or tripping a pump. It is the link between the safety analysis and the shutdown logic programmed into the control system.
What does PSH mean in API 14C?
PSH is a pressure safety high device: a sensor that detects pressure above a safe limit and starts a shutdown. PSL is the low-pressure version. LSH, LSL, TSH and TSL follow the same pattern for level and temperature.
What is the difference between API RP 14C and ISO 10418?
ISO 10418 is the international standard for the basic surface process safety systems on offshore installations, and it uses the same analysis approach. The 2019 edition no longer reproduces the RP 14C safety analysis tables and checklists, and refers to the RP 14C methods instead.
In Deck Twin
The wellhead control panel cites API RP 14C and ISO 10418 for the surface safety valve and shutdown logic it serves, and the drain hub cites RP 14C for typical drain systems. The ESD valve, blowdown valve, pressure safety valve, level switch and pressure switch draw the kinds of device the analysis calls for. The library draws hardware only. It does not carry out a safety analysis or produce a SAFE chart.
Deck Twin uses these standards as reference values for visualisation. Check the current edition of each standard before using any value for design, procurement or fabrication.