API 620

Large, welded, low-pressure storage tanks

API 620 explained: low-pressure welded tanks up to 15 psig, refrigerated storage in Annex R, LNG in Annex Q, and API 620 vs API 650.

Scope

API 620 covers the design and construction of large, welded, field-erected storage tanks that hold liquids or gases at pressures above those allowed by API 650. The basic rules cover tanks with up to 15 psig (103 kPa) in the gas or vapour space and metal temperatures up to 250 °F (121 °C). The tank has a single vertical axis of revolution, so besides cylinders it can be spheroidal or have curved roofs and bottoms shaped to carry the pressure.

Two annexes extend it to cold service. Annex R covers refrigerated products between +40 °F and -60 °F (4 °C and -51 °C), such as refrigerated butane and propane. Annex Q covers liquefied gases down to -325 °F (-198 °C), which includes LNG, liquid nitrogen and liquid oxygen. On oil and gas facilities API 620 tanks are found at LNG plants and import terminals, LPG and NGL terminals, and refineries.

Storage at higher pressure, such as LPG at ambient temperature, uses pressure vessels to ASME Section VIII. Tanks at close to atmospheric pressure use API 650. API 625 covers the whole refrigerated tank system, of which an API 620 inner tank can be one part.

API 620 limits at a glance

ItemCommonly quoted limit
Pressure in the gas or vapour space, basic rulesUp to 15 psig (103 kPa)
Metal temperature, basic rulesUp to 250 °F (121 °C)
Annex R, refrigerated products+40 °F to -60 °F (4 °C to -51 °C)
Annex Q, liquefied gasesDown to -325 °F (-198 °C)

Commonly quoted values, not a copy of the standard. The current document is the 12th edition of October 2013, with Addendum 4 of February 2025 and Errata 1 of March 2025. Check the API catalogue for the current status.

API 620 and the neighbouring tank standards

Which tank standard applies depends on the pressure, the temperature and whether the tank is new. API 650 vs API 620 compares the two design standards in more detail.

StandardUse it for
API 650New welded tanks at close to atmospheric pressure
API 620New welded tanks at low pressure, including refrigerated and cryogenic storage
API 625Refrigerated tank systems as a whole: inner and outer containment, insulation and the system around them
API 653Inspection and repair of API 650 tanks in service
ASME Section VIII and API 2510LPG and other liquids stored under pressure in spheres and bullets

Refrigerated and LNG storage

Cold liquids are stored at close to atmospheric pressure and kept cold by boil-off: a small part of the liquid evaporates and the vapour is taken away and compressed or reliquefied. This is why refrigerated tanks are low-pressure tanks, not pressure vessels.

An LNG tank is usually a tank inside a tank. The inner tank holds the liquid and is made of a material that stays tough at very low temperature, such as 9% nickel steel or stainless steel. The outer tank holds the vapour and the insulation, and in full containment designs it is a concrete wall that can also hold the liquid if the inner tank leaks.

Key concepts

Low pressure
API 620 sits between atmospheric tanks and pressure vessels. The internal pressure is high enough that the roof, the bottom and the joints need a stress analysis. The hydrostatic rules of API 650 are not enough on their own.
Shapes of revolution
Any shape with a single vertical axis of revolution is allowed. Domed roofs, curved bottoms and spheroids carry pressure better than flat plates.
Biaxial stress
Plates in the shell and roof are stressed in two directions at once. The design checks the combined stress at each level, which is why API 620 needs more calculation than API 650.
Material toughness
At low temperature many steels turn brittle. The cold service annexes set materials and impact testing so that the plates and welds stay tough at the lowest metal temperature.
Testing
The finished tank is tested with water and with air pressure in the vapour space. Cold tanks may be tested partly full, because a full water load can be heavier than the product.
Venting
Pressure and vacuum relief protect the tank against overfill, boil-off upsets, fire and vacuum from pumping out. The venting design follows API 2000 and the project relief study.

Questions

What is the difference between API 620 and API 650?

API 650 covers tanks at close to atmospheric pressure, with a small extension to about 2.5 psi under its Annex F. API 620 covers low-pressure tanks up to 15 psig, and its annexes cover refrigerated and cryogenic storage. API 620 tanks need more stress analysis and are often domed or spheroidal.

What is API 620 Annex Q?

Annex Q covers tanks for liquefied gases at temperatures down to -325 °F (-198 °C), such as LNG, liquid nitrogen and liquid oxygen. It sets the materials, design, welding, inspection and testing needed for that cold service.

What is API 620 Annex R?

Annex R covers tanks for refrigerated products between +40 °F and -60 °F (4 °C and -51 °C), such as refrigerated propane, butane and ammonia.

What is the current edition of API 620?

The 12th edition, from October 2013, with addenda issued up to 2025 and an erratum in 2025. Check the API catalogue before you cite it.