API 521

Pressure-relieving and depressuring systems

API 521 guides how to find relief loads, depressure equipment and design flare and vent systems, from overpressure causes to flare radiation.

Scope

API Std 521 covers the analysis of overpressure causes, the calculation of relieving rates, and the design of the systems that take the relief away: headers, knockout drums, flares and vents. It also covers emergency depressuring of equipment through blowdown valves.

On oil and gas facilities it sets the basis for the flare system: which PSVs and BDVs discharge to it, how big the headers and KO drum are, how high the flare stack or how long the flare boom must be, and where a cold vent is acceptable.

API 521 does not size the relief valve itself, which is API 520, or set relief valve dimensions, which is API 526. Flare tips and burners are covered in more detail by API 537. Values such as radiation limits and depressuring targets must be taken from the current edition and the project's own philosophy.

Key concepts

Overpressure scenarios
Each item is checked for credible causes: blocked outlet, external fire, control valve failure, gas blowby from upstream, exchanger tube rupture, loss of cooling or power, and thermal expansion of trapped liquid. The scenario with the highest load sets the relief size.
Fire case
A fire under a vessel heats the wetted surface and boils off liquid, or overheats the gas space. The heat input depends on the wetted area, drainage and fireproofing, and it is a common governing case for vessels.
Depressuring
Blowdown valves vent the gas inventory to flare in an emergency. The aim is to lower the pressure before fire weakens the vessel wall, within a set time agreed for the project.
Flare header and KO drum
The header collects relief from many sources, and its size limits the back pressure on every valve. A knockout drum at the low point separates liquid droplets before the gas reaches the flare tip.
Radiation and dispersion
Stack height or boom length is chosen so that heat radiation at working areas, and at the helideck offshore, stays within acceptable limits. For cold vents, the gas must disperse below its flammable limit before it reaches people or ignition sources.
Purge and seals
A small continuous purge keeps air out of the flare system. A molecular or velocity seal near the tip reduces the purge gas needed.

In Deck Twin

The flare stack and flare boom take a headerNps, pilots, a lit flame and stack height or boom length and angle. The cold vent stack and vent boom add a flame arrestor. The blowdown valve and pressure safety valve are the sources that feed them. The library draws the hardware only. It does not calculate relief loads or radiation, so heights and lengths must come from the project's own flare study.

Deck Twin uses these standards as reference values for visualisation. Check the current edition of each standard before using any value for design, procurement or fabrication.

Components that follow API 521 5