API RP 500 / RP 505

Classification of locations for electrical installations at petroleum facilities

API RP 500 and RP 505 explained: hazardous area classification by Division or Zone, how they map, and how extents are set around equipment.

Scope

API RP 500 and API RP 505 are two recommended practices for classifying hazardous locations at petroleum facilities, so that the right electrical equipment can be chosen for each place. RP 500 uses the North American Class I, Division 1 and Division 2 system. RP 505 covers the same ground with the Class I, Zone 0, Zone 1 and Zone 2 system, which is aligned with the IEC approach.

Both give typical drawings of classified areas around common sources of release: pumps, compressors, vessels, vents, separators, wellheads, tank vents and loading points. Engineers use them to draw the hazardous area layout of a platform or plant. In the US the National Electrical Code recognises both the Division and the Zone systems.

They classify the location. The protection of the equipment used in it, such as flameproof, increased safety or intrinsically safe equipment, is covered by IEC 60079 and the national codes. Both practices cover Class I locations, where the hazard is a flammable gas or vapour, not combustible dusts or fibres.

Division and Zone side by side

Division (RP 500)Zone (RP 505)Meaning in plain words
Division 1Zone 0A flammable atmosphere is present continuously or for long periods
Division 1Zone 1A flammable atmosphere is likely in normal operation
Division 2Zone 2A flammable atmosphere is not likely in normal operation, and if it occurs it lasts only a short time
UnclassifiedUnclassifiedNot expected to contain a flammable atmosphere that needs special electrical equipment

Zone 2 and Division 2 are broadly the same. Division 1 covers both Zone 0 and Zone 1, so Zone 0 has no direct Division equivalent. A commonly quoted mapping, not a copy of either standard.

How an area is classified

  1. 1

    List the flammable materials

    Each fluid is described by its flash point, its density compared with air and its gas group, which sets how easily it ignites.

  2. 2

    Find the sources of release

    Seals, flanges, valves, vents, drains, sample points and openings are each looked at for how often and how long they could release.

  3. 3

    Judge the ventilation

    Open, well-ventilated areas let gas disperse quickly. Enclosed or poorly ventilated areas raise the classification or extend it.

  4. 4

    Set the extent

    The distance around each source comes from the typical figures in the practice, adjusted for the actual equipment, pressure and layout.

  5. 5

    Draw and record

    The result is a hazardous area classification drawing and a schedule that list each source, its grade and its extent.

Which practice to use

In the US both systems can be used at one facility, but the electrical code limits where they meet: a Zone 2 area may adjoin a Division 2 area but not overlap it, and a Zone 0 or Zone 1 area may not adjoin a Division 1 or Division 2 area. Projects that buy IEC-certified equipment or work for international operators often choose Zones. Many existing US onshore plants stay on Divisions.

The current editions are RP 500, 4th edition, June 2023, and RP 505, 3rd edition, January 2025. US offshore regulations still refer to earlier editions of both. Check the API catalogue and the project specification before you cite either.

Key concepts

Class I
Locations where flammable gases or vapours may be present. Class II and Class III cover combustible dusts and fibres, which these practices do not address.
Gas groups
Gases are grouped by how easily they ignite and how a flame passes through gaps. Divisions use groups A to D, and Zones use IIA, IIB and IIC. Hydrogen and acetylene sit in the most severe groups.
Sources of release
Any point from which flammable material can escape. With adequate ventilation, a continuous source usually leads to Zone 0, a primary source to Zone 1 and a secondary source to Zone 2.
Adequate ventilation
Ventilation that keeps gas below its flammable limit and prevents build-up. It is a basis for the typical extents, so enclosed modules need their own assessment.
Temperature class
Equipment in a hazardous area must have a surface temperature below the autoignition temperature of the gas, marked as T1 to T6.
Electrical equipment selection
Once the area is classified, equipment is chosen with a suitable protection method and marking, under IEC 60079 or the national code.

Questions

What is the difference between API RP 500 and API RP 505?

Both classify hazardous locations at petroleum facilities. RP 500 uses Class I, Division 1 and 2. RP 505 uses Class I, Zone 0, 1 and 2, the system used under IEC rules. The method is similar, but the Zone system splits the most hazardous areas into Zone 0 and Zone 1.

Is Zone 1 the same as Division 1?

Not exactly. Division 1 includes everything a Zone system would call Zone 0 or Zone 1. Zone 2 and Division 2 are broadly the same.

Does API RP 505 tell me which equipment to buy?

No. It classifies the location. The equipment is then chosen for that classification using the protection methods in IEC 60079 or the national electrical code. See also ATEX vs IECEx.

In Deck Twin

No component cites API RP 500 or RP 505. Many electrical and instrument components cite IEC 60079 for their protection type, such as the junction box, local control station and point gas detector. The library does not classify areas or check that equipment suits a zone.

Deck Twin uses these standards as reference values for visualisation. Check the current edition of each standard before using any value for design, procurement or fabrication.